Output voltage regulation: Line mode - Sine wave line voltage 120V (-18% / +8%); Battery mode - PWM sine wave output 120V +/-5%
Output frequency regulation: Line mode - Passes line frequency of 60Hz +/-10%; Battery mode - Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type: 8x NEMA 5-15R output receptacles (6 with UPS and surge suppression / 2 with surge suppression only)
Input:
Maximum input amps: 12 A
Input connection type: NEMA 5-15P
Input cord length: 6 ft., 14 gauge
Recommended electrical service: 15A 120V
Battery:
Full load runtime: 5 minutes (1500VA / 940 watts) - add one BP24V14 for 14 minutes
Half load runtime: 14 minutes (750VA / 470 watts) - add one BP24V14 for 34 minutes
DC system voltage: 24 V DC
Typical battery lifespan: 3~6 years, depending on usage
Battery recharge rate: 2~4 hours to 90%
Voltage Regulation:
Overvoltage correction: Input voltages between 128 and 147VAC are reduced by 12%
Direct pass through: Input voltages between 108 and 127VAC are passed on to connected equipment unchanged
Brownout correction: Input voltages between 93 and 107VAC are boosted by 14%
Severe brownout correction: Input voltages between 75 and 92VAC are boosted by 30%
Surge / Noise Suppression:
AC surge suppression: 480 joules
AC suppression response time: Instantaneous
Dataline suppression: Single pair of 8 wire RJ-style phone connectors protects TEL/DSL or ethernet line. Dialup phone suppression on the center two wires with 260V clamping. Ethernet suppression covers pins 1,2,3,6 with 7.5V clamping. Includes phone cable
EMI / RFI AC noise suppression: Yes
Communications:
Network monitoring port: Single built-in USB port supports on battery, low battery, power restored, AC line voltage, DC battery voltage and battery capacity messaging. Interface supports timed inverter shutoff after unattended shutdown, activate self-test and 10 second reboot of connected equipment.
WatchDog compatibility: Yes
Line / Battery Transfer:
Transfer time from line power to battery mode: 2~4 milliseconds
Low voltage transfer to battery power: Switches to battery power as line voltage decreases to 75 volts or less. Resets back to line power mode as line voltage increases to 79V or higher.
High voltage transfer to battery power: Switches to battery power as line voltage increases to 147 volts or higher. Resets back to line power mode as line voltage decreases to 143V or less.
Certifications: Tested to UL1778 (USA), CSA (Canada), NOM (Mexico), FCC Class B (Emissions)
Special Features:
Cold Start: Yes, inverter can be "cold started" to enable temporary AC output during a power failure
Appearance: Attractive gray tower UPS
Physical:
Material of construction: Polycarbonate
Form factors supported: Tower, wall mountable with optional UPSWM accessory
Cooling method: Fan
Battery Access: Battery access door allows user replacement of UPS batteries. Hot-swappable battery replacement supported.
Dimensions (WxDxH): 7.25 x 7.5 x 11.75 inch/ 18.4 x 19.1 x 29.8 cm
Weight: 32.2 lbs / 14.6 kg
* Product descriptions and part numbers are subject to change, and may not reflect manufacturer product changes. Please check the manufacturer's website and use the item's manufacturer part number to find the most up to date product description.